Configuration (system bus − CAN interface)

Tip!

Changes with regard to the CAN baud rate, the CAN addresses, and the identifiers for PDOs only
are accepted after a reset node.

A reset node can be effected by

·

Reconnection of the mains

·

Reset node command via NMT command.

(

^ 2−6)

·

Reset node via C0358

(

^ 3−8)

3.1

CAN baud rate

In order to accomplish communication via the system bus, all nodes have to use the same baud rate
for data transmission.

·

The configuration of the baud rate is effected via code C0351:

Code

LCD

Possible settings

Information

Lenze

Selection

C0351 CAN baud rate

0

0

500 kbit/s

1

250 kbit/s

2

125 kbit/s

3

50 kbit/s

4

1000 kbit/s

System bus − baud rate

·

Save changes with C0003 = 1.

·

Changes are only valid after
reset node!