System bus (CAN) for Lenze PLC devices

CAN system blocks

7.6

CAN_Management (node number: 101)

7−21

L

PLC−Systembus EN 2.0

7.6.2

Outputs_CAN_Management

Variable

Data type

Signal type

Address

Display

code

Display

format

Notes

CAN_bResetNode_b

Bool

Binary

%QX101.0.0

Carry out reset node of the PLC

CAN_bTxCan2Synchronized_b

%QX101.0.1

Transmit CAN2_OUT with sync
telegram.

CAN_bTxCan3Synchronized_b

%QX101.0.2

Transmit CAN3_OUT with sync
telegram.

Note!

If CAN_bTxCan2Synchronized_b and/or CAN_bTxCan3Synchronized_b are integrated, it is required
to configure the device as sync transmitter. The data are transmitted immediately after the sync
signal is sent.

7.6.3

Activating a reset node

A reset node is activated by setting CAN_bResetNode_b to TRUE or C0358 = 1.

Tip!

Even if the CAN_Management SB has not been assigned to the control configuration, a reset node
can be activated via C0358.

(

^ 3−8)

7.6.4

Defining the instant of transmission for CAN2_OUT/CAN3_OUT

Via CAN_bTxCan2Synchonized_b and CAN_bTxCan3Synchonized_b you define the instant of
transmission for the CAN objects CAN2_OUT and CAN3_OUT:

·

FALSE: Data from CAN2_OUT/CAN3_OUT are sent at the end of the process image.

·

TRUE: Data from CAN2_OUT/CAN3_OUT are sent to sync.
– The identifiers for the sync transmission C0369 and reception telegram can be set via

C0367/C0368.

– The sync Tx time can be set via C0369.
– Detailed information on this can be found in the description of the CAN_Syncronization SB.

(

^ 7−23)