2 can boot-up, Can boot−up, System bus (can) for lenze plc devices – Lenze DDS System bus CAN for PLC User Manual

Page 36: 2 can boot−up, Can" system bus interface configuration

Advertising
background image

System bus (CAN) for Lenze PLC devices

"CAN" system bus interface configuration

3−2

l

PLC−Systembus EN 2.0

3.2

CAN boot−up

If the initialisation of the system bus and the associated state change from Pre−operational to
Operational is not taken over by a higher−level master system, the PLC or a controller can be
designated as a "quasi" master to accomplish this task.

·

The configuration is effected via code C0352:

Code

LCD

Possible settings

Information

Lenze

Selection

C0352 CAN mst

0

0

Boot−up not active

1

Boot−up active

Device sends system bus boot−up
and thus is the "quasi" master.

Delay time for system bus initialisation (boot−up)

Some nodes (e. g. HMIs) require a specific starting time after mains connection before they can be
transferred to the Operational state via NMT commands by the master.

In order to ensure that even the node with the greatest starting time really is ready to receive NMT
commands, you can set a delay time. When it has expired, NMT commands can only be transmitted
after mains power−up.

·

The configuration of this delay time is effected via code C0356/1:

Code

LCD

Possible settings

Information

Lenze

Selection

C0356

1

CAN boot−up

3000

0

{1 ms}

65000 Delay time after power−on for

initialisation via the "quasi" master