System bus (can) for lenze plc devices, General information – Lenze DDS System bus CAN for PLC User Manual

Page 30

Advertising
background image

System bus (CAN) for Lenze PLC devices

General information

2−18

l

PLC−Systembus EN 2.0

Telegram from the controller (value of the parameter requested)

Formula

Information

Identifier

= basic identifier + node address
= 1408 + 5
= 1413

·

Basic identifier for parameter data channel 1 (input) = 1408

·

Node address of the controller = 5

Command code = 43

hex

·

"Read Response" command (response to the read request with the
current value)

Index

= index of the read request

Subindex

= subindex of the read request

Data 1 ... 4

= 43 x 10000
= 430000
= 00 06 8F B0

hex

·

Assumption: The current heatsink temperature of the controller is 43 ºC,
therefore the value of the parameter to be read is 43

·

Fixed32 data format (4 fixed decimal positions); multiply value by 10000

11bit

8 bytes user data

Identifier

Command

code

Index

Subindex

Data 1

Data 2

Data 3

Data 4

Low byte

High byte

1413

43

hex

C2

hex

5F

hex

0

B0hex

8Fhex

06

hex

00

hex

(LSB)

(MSB)