System bus (CAN) for Lenze PLC devices

"CAN" system bus interface configuration

3−7

l

PLC−Systembus EN 2.0

3.7

Synchronisation

Tip!

By means of the CAN_Synchronization SB, the internal time base of the PLC can be synchronised
with the arrival of the sync telegram.

Thus, the internal calculating processes (e. g. control−oriented processes) of the PLC can be
synchronised with the calculating processes of other nodes which can also process the sync
telegram.

Detailed information on the CAN_Synchronization SB can be found in chapter 7.7.

(

^ 7−23)

3.7.1

CAN sync response

The response to the reception of a sync telegram can be configured via C0366:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0366 Sync response

1

CAN sync response

0

No response

No response

1

Response to sync

PLC responds to a sync telegram
by sending the CAN1_OUT object.

3.7.2

CAN sync identifiers

The transmission or reception identifiers of the sync telegram can be configured via C0367/C0368:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0367 Sync Rx Id

128

1

{1}

256 CAN sync Rx identifier

Receive identifier of the sync
telegram

C0368 Sync Tx Id

128

1

{1}

256 CAN sync Tx identifier

Transmit identifier of the sync
telegram

3.7.3

CAN sync Tx transmission cycle

The cycle time within which a sync telegram with the identifier set in C0368 is transmitted can be
configured via C0369:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0369 Sync Tx time

0

0

{1}

65000

0 = Off

CAN sync transmission telegram
cycle
A sync telegram with the identifier
of C0368 is sent with the set cycle
time.