4 assignment of the user data to variables, Assignment of the user data to variables, System bus (can) for lenze plc devices – Lenze DDS System bus CAN for PLC User Manual

Page 104: Can system blocks

Advertising
background image

7.4

CAN2_IO (node number: 32)

System bus (CAN) for Lenze PLC devices

CAN system blocks

7−16

L

PLC−Systembus EN 2.0

7.4.4

Assignment of the user data to variables

Several variables of different data types are assigned to the user data to be transmitted and received.
Thus, the data in the PLC program can be optionally interpreted as:

·

binary information (1 bit)

·

status word/quasi−analog value (16 bit)

·

angle information (32 bit)

Variables for user data to be transmitted

User data

Assigned variables

Byte

Bit

Variable (1 bit)

Variable (16 bit)

Variable (32 bit)

1

0

...

7

CAN2_bFDO0_b

...

CAN2_bFDO7_b

CAN2_nOutW1_a

CAN2_dnOutD1_p

2

0

...

7

CAN2_bFDO8_b

...

CAN2_bFDO15_b

3

0

...

7

CAN2_bFDO16_b

...

CAN2_bFDO23_b

CAN2_nOutW2_a

4

0

...

7

CAN2_bFDO24_b

...

CAN2_bFDO31_b

5

0...7

CAN2_nOutW3_a

6

0...7

7

0...7

CAN2_nOutW4_a

8

0...7

Note!

Avoid simultaneous overwriting via different variable types to ensure data consistency.

For instance, if you want to write bytes 1 and 2, only use the variable CAN2_dnOutD1_p,
CAN2_nOutW2_a, or only the variables CAN2_bFDO0_b ... CAN2_bFDO15_b for this purpose!

Variables for received user data

User data

Assigned variables

Byte

Bit

Variable (1 bit)

Variable (16 bit)

Variable (32 bit)

1

0

...

7

CAN2_bInB0_b

...

CAN2_bInB7_b

CAN2_nInW1_a

CAN2_dnInD1_p

2

0

...

7

CAN2_bInB8_b

...

CAN2_bInB15_b

3

0

...

7

CAN2_bInB16_b

...

CAN2_bInB23_b

CAN2_nInW2_a

4

0

...

7

CAN2_bInB24_b

...

CAN2_bInB31_b

5

0...7

CAN2_nInW3_a

6

0...7

7

0...7

CAN2_nInW4_a

8

0...7