System bus (CAN) for Lenze PLC devices

"CAN" system bus interface configuration

3−8

l

PLC−Systembus EN 2.0

3.8

Reset node

Changes with regard to the CAN baud rate, the node addresses and the identifiers only are accepted
after a reset node.

A reset node can be effected by

·

Reconnection of the mains

·

Reset node command via NMT command.

(

^ 2−6)

·

Reset node command via the CAN_Management SB

(

^ 7−20)

·

Reset node via C0358:

Code

LCD

Possible settings

Information

Lenze

Selection

C0358 Reset node

0

0

No function

1

CAN reset node

Reset node

3.9

System bus management

Via the CAN_Management SB,

·

a reset node can be activated.

·

"Communication error" and "Bus off state" can be processed in the PLC program.

·

the instant of transmission of CAN2_OUT and CAN3_OUT can be influenced.

Tip!

Detailed information on the CAN_Management SB can be found in chapter 7.6.

(

^ 7−20)

3.10

Mapping indexes to codes

The operating system as of V6.0 of the Lenze PLCs contains a specific CanDSx driver which can be
activated using the functions of the LenzeCanDSxDrv.lib function library.

(

^ 11−1)

By means of this driver indexes within the PLC can be assigned to another code as the one which
is automatically allocated.

Notes!

·

Each Lenze code is fixedly assigned to an index via the following formula:

Index = 5FFF

hex

− code

Index = 24575

dec

− code

·

The function of the CanDSx driver only is limited to the system bus (CAN).
– For the second FIF−CAN channel provided for the drive PLC, the CanDSx driver cannot be