System bus (CAN) for Lenze PLC devices

General information

2−7

l

PLC−Systembus EN 2.0

2.6

Transmission of process data

Process data are data for control−oriented concerns, e. g. setpoints and actual values.

·

Process data are transferred as so−called PDOs (Process Data Objects) with a high priority via
the system bus.

·

Transmitting and receiving the process data is effected by the use of specific system blocks:

CAN

(integrated)

XCAN

(AIF interface)

FIF−CAN

(FIF interface)

For Drive PLC only!

CANaux

For ECSxA only!

Information

CAN1_IO

AIF1_IO_AutomationInterface

FIF_CAN1_IO

CANaux1_IO

Cyclic process data (sync−controlled)

CAN2_IO

AIF2_IO_AutomationInterface

FIF_CAN2_IO

CANaux2_IO

Event− or time−controlled process data

CAN3_IO

AIF3_IO_AutomationInterface

FIF_CAN3_IO

CANaux3_IO

Event− or time−controlled process data

Tip!

In the following subchapters you’ll receive further information on the CAN1_IO ... CAN3_IO process
data objects of the CAN interface. This information also applies to the process data objects of the
AIF−, FIF− and CAN−AUX interface!

2.6.1

Process data channels

Process data channel 1: CAN1_IO

The CAN1_IO SB can be used for the data exchange of cyclic process data (e. g. setpoints and
actual values) with a higher−level host system.

cyclic process data (sync−controlled)

process data channel 1

CAN1_IN

CAN1_OUT

Host

Fig. 2−2

Process data channel 1 (CAN1_IO) for the cyclic data exchange