1 fif_inputs_can3, 2 fif_outputs_can3, 3 process data telegram – Lenze DDS System bus CAN for PLC User Manual

Page 125: Fif_inputs_can3, Fif_outputs_can3, Process data telegram, System bus (can) for lenze plc devices, Fif−can system blocks

Advertising
background image

8.3

FIF_CAN3_IO (node number: 36)

System bus (CAN) for Lenze PLC devices

FIF−CAN system blocks

8−2

L

PLC−Systembus EN 2.0

8.3.1

FIF_Inputs_CAN3

Variable

Data type

Signal type

Address

Display code

Display

format

Notes

FIF_CAN3_nInW1_a

Integer

Analog

%IW36.0

C2492/8

dec [%]

FIF_CAN3_nInW2_a

%IW36.1

C2492/9

FIF_CAN3_bInB0_b

Bool

Binary

%IX36.0.0

hex

...

...

C2491/5

FIF_CAN3_bInB15_b

%IX36.0.15

FIF_CAN3_bInB16_b

%IX36.1.0

...

...

C2491/6

FIF_CAN3_bInB31_b

%IX36.1.15

FIF_CAN3_dnInD1_p

Double integer

Position

%ID36.0

FIF_CAN3_nInW3_a

Integer

Analog

%IW36.2

C2492/10

dec [%]

FIF_CAN3_nInW4_a

%IW36.3

C2492/11

8.3.2

FIF_Outputs_CAN3

Variable

Data type

Signal type

Address

Display code

Display

format

Notes

FIF_CAN3_nOutW1_a

Integer

Analog

%QW36.0

C2493/8

dec [%]

FIF_CAN3_nOutW2_a

%QW36.1

C2493/9

FIF_CAN3_bFDO0_b

Bool

Binary

%QX36.0.0

...

...

FIF_CAN3_bFDO15_b

%QX36.0.15

FIF_CAN3_bFDO16_b

%QX36.1.0

...

...

FIF_CAN3_bFDO31_b

%QX36.1.15

FIF_CAN3_dnOutD1_p

Double integer

Position

%QD36.0

FIF_CAN3_nOutW3_a

Integer

Analog

%QW36.2

C2493/10

dec [%]

FIF_CAN3_nOutW4_a

%QW36.3

C2493/11

8.3.3

Process data telegram

The process data telegram consists of an identifier and 8 bytes of user data.

11bit

8 bytes user data

Identifier

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Information on the identifier can be found in chapter 2.4.1.

(

^ 2−3)