Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

19

Understand the Operation of Safety Functions

Chapter 2

Using a Test Output with a Safety Input

A test output can be used in combination with a safety input for short circuit
detection. Configure the test output as a pulse test source and associate it to a
specific safety input.

The test output can also be used as a power supply to source 24V DC for an
external input circuit.

Figure 4 - Example Use of a 1791ES-IB16 Module

Table 1 - Typical Pulse Width and Period

Figure 5 - Test Pulse in a Cycle

I8

I9

T8

T9

I10

I11

T10

T11M

I12

I13

T12

T13

I14

I15

T14

T15M

I0

I1

T0

T1

I2

I3

T2

T3M

I4

I5

T4

T5

I6

I7

T6

T7M

IN+ IN-

24V DC

24V DC Output with Test Pulse

External Contact

Safety Input

Attribute

1791ES-IB8XOBV4

1791ES-IB16

Pulse width

500 μs

500 μs

Period

150 ms

150 ms