Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 43

Advertising
background image

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

43

Wiring Examples

Chapter 4

Figure 20 - Limit Switch Dual-channel Inputs and a Manual Reset

This example shows wiring and controller configuration when using the Guard
I/O module with limit switch dual-channel inputs and a manual reset. If used in
combination with the programs of a safety controller, the wiring is Category 4 in
accordance with EN 954-1 wiring requirements.

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Equivalent

Dual-channel Safety Input 0/1 Discrepancy Time

1000 ms (application dependent)

Safety Input 1

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2

Safety Input 2 Channel Mode

Used as Standard Input

Safety Input 2 Test Source

Not Used

Dual-channel Safety Input 2/3 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

Test Output 2

Test Output 2 Mode

Power Supply Output

In +

In -

FE

I0

I1

T0

T1

I2

I3

T2

T3M

S2

(N.O.)

S1

(N.C.)

PS1

S3

44285

PS1: User 24V DC power supply
S!: Safety Limit Switch

(Positive Opening Mechanism)

S2: Safety Limited Switch

Close

Safety
Guard