Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

51

Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

Safety-Readback - This selection is not available for input-only safety

modules. Selecting Safety-Readback creates both safety and readback tags,
with readback indicating the presence of 24V on the output terminal.

Input Status Options

Choose from these options.

None - No status tags, only data for the inputs

IMPORTANT

Status data is not SIL 3 data. Do not use status data to directly control a SIL 3
safety output.