Work with the output configuration dialog – Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 63

Advertising
background image

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

63

Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

Complete entries on the Test Output dialog box, referring to the figure.

Work with the Output
Configuration Dialog

Read this for a guideline on how to configure safety outputs by using the
information in the table and completing the entries referring to the figure.

Table 8 - Guidelines for Configuring Safety Outputs

Parameter Name

Value

Description

Default

Point Operation Type Dual

The 1791ES module treats the outputs as a pair. It always sets them HI to LO as a matched pair.
Safety logic must set both of these outputs ON or OFF at the same time or the module will declare a channel fault.

Dual-channel

Point Mode

Not Used

The output is disabled.

Not Used

Safety

The output point is enabled, and it does not perform a pulse test on the output.

Safety Pulse Test

The output point is enabled and performs a pulse test on the output.
When the output is energized, the output pulses LO briefly. The pulse test detects if 24V remains on the output
terminal during this LO pulse due to a short to 24V or if the output is shorted to another output terminal.

Output Error Latch
Time

0…65,530 ms (in
increments of 10 ms)

The purpose for latching output errors is to make sure that intermittent faults that can only exist for a few
milliseconds are latched long enough to be read by the controller. The amount of time to latch the errors is based
on the RPI, the safety task watchdog, and other application-specific variables.

1000 ms