Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 78

Advertising
background image

78

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Appendix A

Get Diagnostic Status from Modules by Using Explicit Messaging

2. Use the CombinedInputStatus bit to detect if one or more of the I/O

points on the module have a fault.
If any input status bits go to a value of 0 (0 = bad; 1 = good), use an

explicit message to determine which individual data points have
faulted.

Note that you can use the second rung to read the status on mode

transition and once a fault is detected, continue reading until the fault is
corrected.

Place these rungs in the standard task.

See the figures that show the MSG instruction parameters for reading
Instance 869 from the 1791ES-IB16 module. See

Appendix C

of this

manual for a layout of possible instances.

Instance 869 (365 Hex) is 7 bytes in length, so the Destination Tag
IB16MSGdata must be at least 7 bytes in length to hold this data. The size
is DINT[2] or 8 bytes.

Advertising
This manual is related to the following products: