Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

Save and Download the
Module Configuration

We recommend that after a module is configured you save your work.

If after downloading the program the MS and NS LED indicators on the Guard
I/O module are not both solid green, this can be due to loss of ownership. The
ownership is based on the following:

Guard I/O EtherNet IP address
Guard I/O safety network number
GuardLogix slot number
GuardLogix safety network number
Path from GuardLogix controller to Guard I/O module
Configuration signature

If any of these change, the connection between the GuardLogix controller and
the Guard I/O module is lost, and the yellow yield in the project tree appears.
Reset ownership to reestablish the connection by using this procedure.

1. Open the safety I/O module properties.

2. Choose the Safety tab.

3. From the dialog box, choose Reset ownership.