68

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Chapter 6

Interpret Module Indicators

Table 10 - 24V DC Output Power Indicator

State

Status

Description

Recommended Action

Off

No power

No power is applied.

Apply power to this section.

Solid green

Normal operation

The applied voltage is within specifications.

None.

Solid yellow

Output power out of specification

The output power is out of specification.

Check your connectors, wiring, and voltages.

Table 11 - Module Status Indicator

State

Status

Description

Recommended Action

Off

No power

No power is applied to the power connector.

Apply power to this connector.

Solid green

Normal operation

The module is operating normally.

None.

Solid red

Unrecoverable fault

The module detected an unrecoverable fault.

Cycle power to the module. If problem persists,
replace the module.

Flashing red and
green

Module is unconfigured

Module needs commissioning due to missing, incomplete, or
incorrect configuration.

Reconfigure the module. For additional
information, inspect Network Status indicator.

Device in self test

The module is performing its power-cycle diagnostic tests.

Wait for the module to complete its power-cycle
diagnostics.

Flashing green

Idle

Idle, waiting for connection from scanner.

Establish connection.

Flashing red

Recoverable fault

The module has detected a recoverable fault.

Cycle power to the module or reset the module.

User-initiated firmware update in progress

User-initiated firmware update is in progress.

Wait for firmware update to complete.

Table 12 - Network Status Indicator

State

Status

Description

Recommended Action

Off

Module not online

The module does not have an IP address.

Verify your network is working properly.

Flashing green Module online with no connections in

established state

The module has acquired an IP address, but no connections are established. Verify your network and module

configuration.

Solid green

Module online with connections in
established state

The module is operating normally.

None.

Flashing red

One or more I/O connections in timed-out
state

The module detected a recoverable network fault.

Verify your network and module
configuration.

User-initiated firmware update

User-initiated firmware update is in progress.

Wait for firmware update to complete.

Solid red

Critical link failure

The module detected an error that prevents it from communicating on the
network, such as duplicate IP address has been detected.

Cycle power to the module. Check network
IP addressing.

Flashing red
and green

Self test

The module is performing its power-cycle diagnostic test.

Wait for the module to complete its power-
cycle diagnostics.