Interpret Module Indicators

Chapter 6

Configuration Lock Indicator

Configuration lock indicator is not supported by the Logix Designer application.

Table 13 - Network Activity Indicator

State

Status

Recommended Action

Off

No link established

Establish link.

Flashing Green

Transmit or receive activity

None.

Steady Green

Link established

None.

Table 14 - Safety Input Status Indicator

State

Status

Description

Recommended Action

Off

Safety input off

The safety input is off or the channel is configured for not used.

Turn the safety input on or reconfigure the
channel, if desired.

Solid yellow

Safety input on

The safety input is on.

None.

Solid red

Fault detected

A fault in the external wiring or input circuit detected.

Check configuration, field wiring, and devices. If no
problem found, replace module.

Flashing red

Partner fault detected

A fault in the partner input circuit of a dual-input configuration
detected.

Check the field wiring and verify your configuration
for the partner circuit. If no problem found, replace
module.

Table 15 - Test Output Status Indicator

State

Status

Description

Recommended Action

Off

Test output off

The test output is off or the channel is configured for not used.

Turn the test output on or reconfigure the channel, if
desired.

Solid yellow

Output on

Output is on.

None.

Solid red

Fault detected

A fault in the external wiring or input circuit detected.

Check field wiring. If no problem found, replace
module. For outputs configured for muting could
indicate undercurrent or burned-out lamp.

Table 16 - Safety Output Status Indicator (1791ES-IB8XOBV4 only)

State

Status

Description

Recommended Action

Off

Safety output off

The safety output is off or the channel is configured for not used. Turn the safety output on or reconfigure the channel, if

desired.

Solid yellow

Safety output on

The safety output is on.

None.

Solid red

Fault detected

A fault in the output circuit was detected.

Check the circuit wiring and end device. If no problem
found, replace module.

Both tags in a dual channel circuit do not have the same value.

Make sure logic is driving tag values to the same state
(off or on).

Flashing red

Partner fault detected

A fault in the partner output circuit of a dual output configuration
was detected.

Check the circuit wiring and end device of the partner. If
no problem found, replace module.