Get Diagnostic Status from Modules by Using Explicit Messaging

Appendix A

The first 32 bits of the instance are in IB16MSGdata[0].0…31, and the
final 24 bits are in IB16MSGdata[1].0…23. Map these 56 bits according to
Instance 869. An easy method to do this mapping is to create a user
defined tag (UDT) for Instance 869. Once you complete this, it appears
as follows.

I/O Data Supported by Each
Module

See the table that shows a summary of default I/O data by module.

The tables show the I/O data supported by each module. Refer to I/O Assembly
Data for data arrangements.

Table 17 -Default I/O Data

Safety Connection

Assembly Instance (Hex)

1791ES-IB16

Safety

225 and 23

1791ES-IB8XOBV4

Safety

204 and 234