Safety Data
Figure 24 - PFD versus Proof Test Interval 1791ES-IB16
Table 27 - Calculated Values for Probability of Failure on Demand (PFD), Probability of Failure per
Hour (PFH), and Mean Time To Failure (MTTF)
Figure 25 - PFD versus Proof Test Interval 1791ES-IB8XOBV4
Cat. No.
Proof Test Interval
PFD
(1/hour)
PFH
(1/hour)
Spurious
Trip Rate
(STR)
MTTF (years)
Year
Hour
1791ES-IB16
1
8760
2.06E-06 4.98E-10
3.309E-06
34.48
2
17520
4.13E-06
5
43800
1.03E-05
10
87600
2.06E-05
1791ES-IB8XOBV4
1
8760
2.09E-06 5.04E-10
5.612E-06
20.33
2
17520
4.17E-06
5
43800
1.04E-05
10
87600
2.09E-05