Safety Data

Figure 24 - PFD versus Proof Test Interval 1791ES-IB16

Table 27 - Calculated Values for Probability of Failure on Demand (PFD), Probability of Failure per
Hour (PFH), and Mean Time To Failure (MTTF)

Figure 25 - PFD versus Proof Test Interval 1791ES-IB8XOBV4

Cat. No.

Proof Test Interval

PFD
(1/hour)

PFH
(1/hour)

Spurious
Trip Rate
(STR)

MTTF (years)

Year

Hour

1791ES-IB16

1

8760

2.06E-06 4.98E-10

3.309E-06

34.48

2

17520

4.13E-06

5

43800

1.03E-05

10

87600

2.06E-05

1791ES-IB8XOBV4

1

8760

2.09E-06 5.04E-10

5.612E-06

20.33

2

17520

4.17E-06

5

43800

1.04E-05

10

87600

2.09E-05