Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

93

Appendix

C

Configuration Reference Information

Understand Parameter
Groups

The modules have these parameter groups: general parameters, safety input, test
output, safety output.

See the tables for the settings in each parameter group. All parameters are set by
using the Logix Designer application.

Topic

Page

Understand Parameter Groups

93

Table 28 - General Parameters

Parameter Name

Value

Description

Default

Safety Output Error Latch Time

0…65,530 ms
(in increments of 10 ms)

Safety output errors are latched for this time.

1000 ms

Safety Input Error Latch Time

0…65,530 ms
(in increments of 10 ms)

Safety input or test output errors are latched for this time.

1000 ms

Table 29 - Safety Input Parameters

Parameter Name

Value

Description

Input Point Operation Type

Single Channel

Use as single channel.

Dual-channel Equivalent

Use as dual-channel. Normal when both channels are ON or OFF.

Dual-channel Complementary

Use as dual-channel. Normal when one channel is ON and the other channel is OFF.

Input Point Mode

Not Used

External input device is not connected.

Safety Test Pulse

Use with a contact output device and in combination with a test output. By using this setting, short-
circuits between input signal lines and the power supply (positive side) and short-circuits between
input signal lines can be detected.

Safety

A solid-state output safety sensor is connected.

Standard

A standard device, such as a reset switch, is connected.

Safety Input Test Source

Not Used

The test output that is used with the input.
n is dependent on the module catalog number.

Test Output 0 to n

Input Delay Time
Off -> On

0…126 ms (in increments of
6 ms)

Filter time for OFF to ON transition

Input Delay Time
On -> Off

0…126 ms (in increments of
6 ms)

Filter time for ON to OFF transition

IMPORTANT

When configuring a test output for Pulse Test mode, verify the
corresponding safety input is configured for safety pulse test.