26

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Chapter 2

Understand the Operation of Safety Functions

Safety Input Fault Recovery

If an error is detected, the safety input data remains in the off state. The
procedure for activating the safety input data again is as follows.

1. Remove the cause of the error.

2. Place the safety input (or safety inputs) into the safety state.

The safety input status turns on (fault cleared) after the input-error latch
time has elapsed. The I/O indicator (red) turns off. The input data can
now be controlled.

Input Delays

On-delay - An input signal is treated as logic 0 during the on-delay time (0…126
ms, in increments of 6 ms) after the input contact’s rising edge. The input only
turns on if the input contact remains on after the on-delay time has elapsed. This
helps prevent rapid changes of the input data due to contact bounce.

Figure 10 - On-delay

Off-delay - An input signal is treated as logic 1 during the off-delay time (0…126
ms, in increments of 6 ms) after the input contact’s falling edge. The input only
turns off if the input contact remains off after the off delay time has elapsed. This
helps prevent rapid changes of the input data due to contact bounce.

Figure 11 - Off-delay

44094

ON

OFF

ON

OFF

Remote I/O

Data Safety

Input

Input Signal

ON-delay

On-delay

ON
OFF

ON
OFF

Input Signal

Remote I/O
Data Safety
Input

44094

OFF

ON

OFF

Safety Input

Input Signal

OFF-delay

Remote I/O Data

44095

Remote I/O Data
Safety Input

Off-delay

Input Signal

ON
OFF

ON
OFF