Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 87

Advertising
background image

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

87

Get Diagnostic Status from Modules by Using Explicit Messaging

Appendix A

3A4 (932)

1791ES-
IB8XOBV4

Standard Only

0

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Output
Power
Error

Input Power
Error

1

Safety
Output 7
Monitor

Safety
Output 6
Monitor

Safety
Output 5
Monitor

Safety
Output 4
Monitor

Safety
Output 3
Monitor

Safety
Output 2
Monitor

Safety
Output 1
Monitor

Safety
Output 0
Monitor

2

Test Output
7 Status

Test Output
6 Status

Test Output
5 Status

Test Output
4 Status

Test Output
3 Status

Test Output
2 Status

Test
Output 1
Status

Test Output
0 Status

(1) This data is only diagnostic data and does not have safety integrity.

Table 22 - Output Data

Instance
(hex)

Module

Connection
Type

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

22 (34)

1791ES-
IB8XOBV4

Safety and
Standard

0

Standard
Output 7

(1)

Standard
Output 6

Standard
Output 5

Standard
Output 4

Standard
Output 3

Standard
Output 2

Standard
Output 1

Standard
Output 0

23 (35)

1791ES-
IB16

Safety and
Standard

0

Standard
Output 7

Standard
Output 6

Standard
Output 5

Standard
Output 4

Standard
Output 3

Standard
Output 2

Standard
Output 1

Standard
Output 0

1

Standard
Output 15

Standard
Output 14

Standard
Output 13

Standard
Output 12

Standard
Output 11

Standard
Output 10

Standard
Output 9

Standard
Output 8

234 (564)

1791ES-I
B8XOBV4

Safety Only

0

Safety
Output 7

Safety
Output 6

Safety
Output 5

Safety Output
4

Safety
Output 3

Safety
Output 2

Safety
Output 1

Safety
Output 0

2C4 (708)

1791ES-
IB8XOBV4

Safety Only

0

Safety
Output 7

Safety
Output 6

Safety
Output 5

Safety Output
4

Safety
Output 3

Safety
Output 2

Safety
Output 1

Safety
Output 0

1

Standard
Output 7

Standard
Output 6

Standard
Output 5

Standard
Output 4

Standard
Output 3

Standard
Output 2

Standard
Output 1

Standard
Output 0

(1) Standard output signifies a Test Output configured as a standard output.

Table 21 - Input Data (continued)

Instance
Hex
(Decimal)

Module

Connection
Type

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Advertising