Chapter 4

Wiring Examples

Figure 17 - Two-hand Monitor

This example shows wiring and controller configuration when using the Guard
I/O module. If used in combination with the programs of a safety controller, the
wiring is Category 4 in accordance with EN 954-1 wiring requirements.

I0

I2

I1

I3

IN+

IN-

T0

T1

E1

T1

T2

T1

T3

S11

31803-M

S12

-

+

FE

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual Channel Safety Input 0/1 Mode

Dual Channel Complementary

Dual Channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2

Safety Input 2 Channel Mode

Test Pulse from Test Output

Safety Input 2 Test Source

Test Output 0

Dual Channel Safety Input 2/3 Mode

Dual Channel Complementary

Dual Channel Safety Input 2/3 Discrepancy Time

100 ms (application dependent)

Safety Input 3

Safety Input 3 Channel Mode

Test Pulse from Test Output

Safety Input 3 Test Source

Test Output 1

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output