Values and states of tags – Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

55

Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

Values and States of Tags

This table shows the values and states of the tags.

Table 5 - Values and States of Tags

Data

Description

Input data

Safety Input Data
SAFETY

Indicates the ON/OFF status of each input circuit.

· ON: 1 OFF: 0

Combined Safety Input Status
SAFETY

An AND of the status of all input circuits.

· All circuits are normal: 1
· An error was detected in one or more input circuits: 0

Individual Safety Input Status
SAFETY

Indicates the status of each input circuit.

· Normal: 1 Fault (Alarm): 0

Combined Safety Output Status
SAFETY

An AND of the status of all safety output circuits.

· All circuits are normal: 1
· An error has been detected in one or more output circuits: 0

Individual Safety Output Status
SAFETY

Indicates the status of each safety output circuit.

· Normal: 1 Fault (Alarm): 0

Muting Lamp Status
SAFETY

Indicates the status when circuit T3 is configured as the muting lamp output.

· Normal: 1 Fault (Alarm): 0

Output Readback
STANDARD

Monitors the presence of 24V on the output circuit. Readback is ON (1) if 24V is on output terminal.

· ON: 1 OFF: 0

Individual Test Output Status
STANDARD

Indicates the status of each of the test output circuits.

· Normal: 1 Fault (Alarm): 0

Output data

Safety Output Data
SAFETY

Controls the safety output.
ON: 1 OFF: 0

Standard Output Data
STANDARD

Controls the test output when Test Output mode is set to a standard output.
ON: 1 OFF: 0

IMPORTANT

Safety denotes information the controller can use in safety-related functions.
Standard denotes additional information that must not be relied on for safety
functions.