50

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

c. For Description, if desired, type a description.

For a detailed explanation of the safety network number (SNN), see the
GuardLogix Controller Systems Safety Reference Manual listed in the
Additional Resources on

page 7

, noting that in most cases, you use the

default provided by the Logix Designer application.

d. Click Change to see the Module Definition dialog box.

e. From the Module Definition dialog box, select values to configure what

data and status tags to generate implicitly for the safety module, noting
that you can configure Input Data, Input Status, and Output Data.

Input Data Options

Choose from these options:

Safety - Selecting Safety creates these tags for the target module:

RunMode: Module mode
ConnectionFaulted: Communication status
Safety Data: Safety inputs from module