Configuration Reference Information

Appendix C

Table 32 - Safety and Standard Data

Data

Description

Input data

Safety Input Data Safety

Indicates the ON/OFF status of each input circuit.
ON: 1
OFF: 0

Combined Safety Input Status Safety

An AND of the status of all input circuits.
All circuits are normal: 1
An error was detected in one or more input circuits: 0

Individual Safety Input Status Safety

Indicates the status of each input circuit.
Normal: 1
Fault (Alarm): 0

Combined Safety Output Status Safety

An AND of the status of all safety output circuits.
All circuits are normal: 1
An error has been detected in one or more output circuits: 0

Individual Safety Output Status Safety

Indicates the status of each safety output circuit.
Normal: 1
Fault (Alarm): 0

Muting Lamp Status Safety

Indicates the status when circuit T3 is configured as the muting lamp output.
Normal: 1
Fault (Alarm): 0

Safety Output Monitor Standard

Monitors the outputs of the safety output circuits.
ON: 1
OFF: 0

Individual Test Output Status Standard

Indicates the status of each of the test output circuits.
Normal: 1
Fault (Alarm): 0

Output data

Safety Output Data Safety

Controls the safety output.
ON: 1
OFF: 0

Standard Output Data Standard

Controls the test output when test output mode is set to a standard output.
ON: 1
OFF: 0

Advertising