Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 89

Advertising
background image

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

89

Get Diagnostic Status from Modules by Using Explicit Messaging

Appendix A

Table 26 - Setting Hold/Clear for Communications Errors (Test Output)

Explicit Message

Service

Function

Command (hex)

Response
(hex)

Service
Code

Class
ID

Instance
ID

Attribute ID

Data Size

Setting for Output
State (Hold or
Clear) after
Communication
Error

Get
Attribute
Single

Reads whether hold or clear is set as the output
state after a communication error for a test
output specified by the instance ID. The setting
can be read for a specified number of points.

0E

09

01…08

05

-

1 byte
00: Clear
01: Hold

Setting for Output
State (Hold or
Clear) after
Communication
Error

Set
Attribute
Single

Sets whether hold or clear as the output status
after a communication error for an output
specified by the instance ID. Sets whether a test
output must hold its state or clear (turn off)
after a communication error.

10 09

01…08

05

1

byte

00: Clear
01: Hold