Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

45

Wiring Examples

Chapter 4

Figure 22 - Dual-load Bipolar Outputs

The example shows wiring and configuration when using the Guard I/O module
with solid state outputs in Dual-channel mode.

Note that all safety outputs of this Guard I/O module are permanently
configured for use as Dual-channel mode only. When used in combination with
the programs of the safety controller, this circuit configuration is Safety Category
4 in accordance with EN 954-1 requirements.

IMPORTANT

In order for the bipolar safety outputs to work correctly, you must connect the devices that are being controlled as
shown in this figure. Connection of devices directly to 24V DC, 0V DC, or Ground is strictly prohibited.

In +

In -

FE

I0

I1

T0

T1

I2

I3

T2

T3M

PS1

FE

O0

P

O1

M

L-

S+

O2

P

O3

M

L-

S+

Out

+

Out

-

PS2

K2

K1

K1

K2

M

k2

K1

44288

PS1, PS2: User 24V DC power supply
(A single power supply can be used
for both input and output power)

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0

Safety Output 0 Channel Mode

Safety Pulse Test

Safety Output 1

Safety Output 1 Channel Mode

Safety Pulse Test