Understand the Operation of Safety Functions

Chapter 2

Safety Outputs

Read this section for information about safety outputs.

Safety Output with Test Pulse

When the safety output is on, the safety output can be test pulsed, as shown in
the figure and table.

By using this function, short-circuits between output signal lines and the power
supply (positive side) and short-circuits between output signal lines can be
detected. If an error is detected, the safety output data and individual-safety
output status turns off.

Figure 12 - Test Pulse in a Cycle

Attribute

1791ES-IB8XOBV4

Pulse width

700 μs

Period

600 ms

IMPORTANT

To prevent the test pulse from causing the connected device to
malfunction, pay careful attention to the input response time of the device.

44096

OUT

On

Off

Typical
700 μs

Typical
600 ms