Dual-channel setting, Safety output fault recovery, Controlling devices – Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 28: Dual-channel setting safety output fault recovery

Advertising
background image

28

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Chapter 2

Understand the Operation of Safety Functions

Dual-channel Setting

When the data of both channels is in the on state, and neither channel has a fault,
the outputs are turned on. The status is normal. If a fault is detected on one
channel, the safety output data and individual safety output status turn off for
both channels.

Figure 13 - Dual-channel Setting (not to scale)

Safety Output Fault Recovery

If a fault is detected, the safety outputs are switched off and remain in the off
state. The procedure for activating the safety output data again is as follows.

1. Remove the cause of the error.

2. Place the safety output (or safety outputs) into the safety state.

The safety output status turns on (fault cleared) when the output-error
latch time has elapsed. The I/O indicator (red) turns off. The output data
can now be controlled.

Controlling Devices

See the table for information about controlling devices.

ON

OFF

OUT0

Safety Output
Status 0, 1

OUT0

OUT1

OUT1

Safety Output
Status 0, 1

Fault Detection

Error
Detected

Remote
I/O
Data

Remote
I/O
Data

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Normal Operation

ATTENTION: Use appropriate devices as indicated in the Controlling
Device Requirements table. Serious injury can occur due to loss of safety
functions.