Examples of wiring – Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual

Page 39

Advertising
background image

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

39

Wiring Examples

Chapter 4

Examples of Wiring

Read this section for examples of wiring by application. See catalog number
details for appropriate module.

Figure 16 - Emergency Stop Switch Dual-channel Inputs with Manual Reset

This example shows wiring and controller configuration when using the Guard
I/O module. If used in combination with the programs in a safety controller, this
wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements.

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Equivalent

Dual-channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2

Safety Input 2 Channel Mode

Used as standard input

Safety Input 2 Test Source

Not Used

Dual-channel Safety Input 2/3 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

Test Output 2

Test Output 2 Mode

Power Supply Output

In +

In -

FE

I0

I1

T0

T1

I2

I3

T2

T3M

S2

PS1

S1

44281

PS1: User 24V DC power supply
S1: Emergency Stop Switch

(Positive Opening Mechanism)