Add a switch to the i/o configuration tree – Rockwell Automation 1783-BMxxx Stratix 5700 Ethernet Managed Switches User Manual User Manual

Page 191

Advertising
background image

Rockwell Automation Publication 1783-UM004E-EN-P - June 2014

191

Manage the Switch via the Studio 5000 Environment Chapter 5

Configuration data (requires password)

IP address method: DHCP, static
IP address, subnet mask, default gateway (all if static)
Host name
Contact name
Geographic location
Port configuration per port: enable/disable, autonegotiate, forced

speed/duplex

Authorized MAC ID per port
Unicast rate limiting threshold per port: in packets per second, bits per

second, or percentage

Multicast rate limiting threshold: in packets per second, bits per sec, or

percentage

Broadcast rate limiting threshold: in packets per second, bits per sec, or

percentage

Smartport assignment per port: role and VLAN

Save and restore of switch configuration (via File Obj)

Add a Switch to the I/O
Configuration Tree

To add the switch to the controller’s I/O tree, follow these steps.

1. Open the project file for the controller that monitors the switch.

2. Select the Ethernet module through which the controller communicates

with the switch.

In this example, the switch communicates through a 1769-L32E
CompactLogix EtherNet/IP controller.

3. Right-click the Ethernet port you created and choose New Module.

4. Click Communications.

IMPORTANT

These steps are required before you can go online to configure and monitor the

switch.

Advertising