Rockwell Automation Publication 1783-UM004E-EN-P - June 2014

Chapter 2 Switch Installation

For 10/100 ports and 10/100/1000 ports, the cable length from a switch

to an attached device cannot exceed 100 m (328 ft).

The fiber-optic cable length from a switch to an attached device cannot

exceed the distance specified in

Appendix C

.

For maximum noise immunity, shielded cables must be used on the RJ45

uplink ports (Gi1/1 and Gi1/2) on these switches:

1783-BMS06TGL
1783-BMS06TGA
1783-BMS10CGL
1783-BMS10CGA
1783-BMS10CGN
1783-BMS10CGP
1783-BMS12T4E2CGNK
1783-BMS12T4E2CGP
1783-BMS12T4E2CGL
1783-BMS20CGL
1783-BMS20CGN
1783-BMS20CGP
1783-BMS20CGPK

Temperature surrounding the unit does not exceed 60 °C (140 °F).

Clearance to front and rear panels meets these conditions:

Front-panel status indicators can be easily read.
Access to ports is sufficient for unrestricted cabling.
Front-panel direct current (DC) power connectors and the alarm relay

connector are within reach of the connection to the DC power source.

Cabling is away from sources of electrical noise, such as radios, power lines,

and fluorescent lighting fixtures.

Connect the unit to only a Class 2 DC power source.

IMPORTANT

When the switch is installed in an industrial enclosure, the

temperature within the enclosure is greater than normal room
temperature outside the enclosure.

The temperature inside the enclosure cannot exceed 140 °F (60 °C), the

maximum ambient enclosure temperature of the switch.

ATTENTION: Do not wire more than 1 conductor on any single terminal.