194

Rockwell Automation Publication 1783-UM004E-EN-P - June 2014

Chapter 5 Manage the Switch via the Studio 5000 Environment

6. Complete the fields on the Module Definition dialog box.

Field

Description

Revision

The major and minor revision of the switch:

Major revision: a number from 1…128
Minor revision: a number from 1…255

Electronic Keying

Compatible Module (default)
Exact Match
Disable Keying

Connection

Input Data (default): Enables only the input data connection
Data: Enables input and output data connection
ATTENTION: This selection enables output tags, which can disable ports and interrupt connections to and through the switch. You can disable
a switch port by setting the corresponding bit in the output tag. The output bits are applied every time the switch receives the output data from
the controller when the controller is in Run mode. When the controller is in Program mode, the output bits are not applied.

The port is enabled if the corresponding output bit is 0. If you enable or disable a port by using the Device Manager Web interface or the CLI, the

port setting can be overridden by the output bits from the controller on the next cyclic update of the I/O connection. The output bits always
take precedence, regardless of whether the Device Manager Web interface or CLI was used to enable or disable the port.

Data Connection Password

Enter the password for accessing the switch. Required only for Data connection.