Switch Installation Chapter 2
5. Use a ratcheting torque flathead screwdriver to torque the alarm relay
connector captive screw (above the installed wire leads) to 0.23 N•m
(2.0 lb•in).
Do not exceed the recommended torque.
6. Repeat the above procedure to insert the input and output wires of one
additional external alarm device into the alarm relay connector.
The following figure shows the completed wiring for two external alarm
devices. The first alarm device circuit is wired as an alarm relay input
circuit—the IN1 and REF connections complete the circuit. The second
alarm device circuit is wired as an alarm relay output circuit by using the
normally open side of the form C relay contacts. The NO and COM
connections complete the circuit.
32288-M
IN1 - External Device Connection 1
REF - External Device Connection 2
IN1—External Device Connection 1
REF—External Device Connection 2
COM—Wired Connection
NO—Wired Connection
32289-M