40

Rockwell Automation Publication 1783-UM004E-EN-P - June 2014

Chapter 2 Switch Installation

5. Insert the ground screw into the functional ground screw opening on the

front panel.

6. Use a ratcheting torque screwdriver to tighten the ground screws and ring

terminal lugs to the switch front panel to 0.4 N

m (3.5 lb

in).

Do not exceed the recommended torque.

7. Attach the other end of the ground wire to a grounded bare metal surface,

such as a ground bus, a grounded DIN rail, or a grounded bare rack.

Wire the Switch DC Power Source

To wire the DC power source for the switch, follow these steps.

ATTENTION: Before performing any of the following procedures, make sure
that power is removed from the DC circuit or the area is nonhazardous before
proceeding:

This product is intended to be supplied by a Class 2 power source marked with

‘Class 2’ and rated from 12, 24, or 48V DC, 2.5 A.

To comply with the CE Low Voltage Directive (LVD), this equipment must be

powered from a source compliant with the safety extra low voltage (SELV) or
protected extra low voltage (PELV).

A readily accessible two-poled disconnect device must be incorporated in the

fixed wiring.

This product relies on the building’s installation for short-circuit (overcurrent)

protection. Make sure that the protective device is rated not greater than 3 A.

Installation of the equipment must comply with local and national electrical

codes.

Allow only trained and qualified personnel to install, replace, or service this

equipment.

ATTENTION: For wire connections to the power and relay connector, you must
use UL- and CSA-rated, style 1007 or 1569 twisted-pair copper appliance wiring
material (AWM) wire.

32276-M

Ring Terminal Lug (single lug shown)