Chapter 2 Switch Installation

The labels for the alarm relay connector are on the switch panel.

To wire the switch to an external alarm device, follow these steps.

1. Loosen the captive screws that hold the alarm relay connector on the

switch, and remove the connector from the switch chassis.

2. Measure two strands of twisted-pair wire (18…20 AWG) long enough to

connect to the external alarm device.

Choose between setting up an external alarm input or output circuit.

3. Use a wire stripper to remove the casing from both ends of each wire to 6.3

mm (0.25 in.) ± 0.5 mm (0.02 in.).

Do not strip more than 6.8 mm (0.27 in.) of insulation from the wires.
Stripping more than the recommended amount of wire can leave exposed
wire from the alarm relay connector after installation.

4. Insert the exposed wires for the external alarm device into the connections

based on an alarm input or output circuit setup. See

Table 1 on page 50

.

Table 1 - Alarm Relay Connector Labels

Label

Connection

NO

Alarm Output Normally Open (NO) connection

COM

Alarm Output Common connection

NC

Alarm Output Normally Closed (NC) connection

IN2

Alarm Input 2

REF

Alarm Input Reference Ground connection

IN1

Alarm Input 1

32287-M