Switch Installation Chapter 2

Power supply requirements depend on your application.

1. Measure a length of 0.82…0.52 mm

2

(18…20 AWG) copper wire long

enough to connect to the DC power source.

2. Using an 18-gauge wire-stripping tool, strip each of the two wires to

6.3mm (0.25 in.) ± 0.5 mm (0.02 in.).

Do not strip more than 6.8 mm (0.27 in.) of insulation from the wire.
Stripping more than the recommended amount of wire can leave wire
exposed after installation.

3. Locate the power connector.

4. Insert the exposed part of the positive wire into the DC+ connection and

the exposed part of the return wire into the DC- connection.

Make sure that you cannot see any wire lead. Only wire with insulation can
extend from the connector.

5. Use a ratcheting-torque screwdriver to torque the power connector captive

screws (above the installed wire leads) to 0.23 N•m (2.0 lb•in).

6. Connect the other end of the positive wire (the one connected to DC+) to

the positive terminal on the DC power source, and connect the other end
of the return wire (the one connected to DC-) to the return terminal on
the DC power source.

Application

Power Supply per Port

Power Consumption

Allen-Bradley Products

PoE only
IEEE 802.3af

44…57V DC (48V DC nom) 15.4 W, max

Switched mode power supplies:
1606-XL Standard
1606-XLE Essential
1606-XLP Compact
1606-XLS Performance

PoE and PoE +
IEEE 802.3at Type 2

50…57V DC (54V DC nom) 15.4 W, max for PoE

30 W, max for PoE+

WARNING: Before performing any of the following procedures, make sure that
power is removed from the DC circuit or the area is nonhazardous before
proceeding.

ATTENTION: If multiple power sources are used, do not exceed the specified
isolation voltage.