37

Switch Installation Chapter 2

To attach the switch to a DIN rail, follow these steps.

1. Position the rear panel of the switch directly in front of the DIN rail,

making sure that the DIN rail fits in the space between the two hooks near
the top of the switch and the spring-loaded latch near the bottom.

2. Holding the bottom of the switch away from the DIN rail, place the two

hooks on the back of the switch over the top of the DIN rail.

3. Push the switch toward the DIN rail to cause the spring loaded latch at the

bottom rear of the switch to move down and snap into place.

ATTENTION: Under certain conditions, viewing the optical port may expose the
eye to hazard. When viewed under some conditions, the optical port may
expose the eye beyond the maximum permissible exposure recommendations.

ATTENTION: Class 1 laser product. Laser radiation is present when the system is
open and interlocks bypassed. Only trained and qualified personnel should be
allowed to install, replace, or service this equipment.

ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.

32285-M

Advertising