Understanding drive fault behavior – Rockwell Automation 2090 Ultra3000 Servo Drives Integration Manual User Manual

Page 105

Advertising
background image

Publication 2098-IN005C-EN-P — March 2008

Troubleshooting Your Ultra3000 Servo Drive

105

Understanding Drive Fault Behavior

The following RSLogix 5000 fault actions are configurable from the
Axis Properties dialog, Fault Actions tab.

RSLogix 5000 Drive Fault Action Definitions

Ultraware software handles all hard faults by disabling the drive.
RSLogix 5000 software provides the four fault handling options,
however, for the Ultra3000 drives, only Shutdown and Disable Drive
are active settings and both result in a coast-to-stop condition. Disable
Drive is the default fault action for all attributes and only selected
faults are programmable. In the Drive Fault Behavior table on
page 106, the controlling attribute is given for programmable fault
actions.

RSLogix 5000 Axis Properties - Fault Actions Tab

Refer to Appendix C, beginning on page 141, for information on how
to reduce unexpected motion as a result of feedback signal loss and
setting the Position Error fault action.

Drive Fault Action

Definition

Shutdown

The drive disables and the contactor enable relay opens. Uncontrolled stop,
motor coasts to a stop.

Disable Drive

The drive is disabled. Uncontrolled Stop, motor coasts to a stop.

Stop Motion

N/A. Drive continues to operate. Status is provided by the Module Status
Indicator.

Status Only

Drive continues to operate. Status is provided by the Module Status
Indicator.

Default setting for Motor

Overtemperature fault (E04).

Advertising
This manual is related to the following products: