Troubleshooting Your Ultra3000 Servo Drive

107

DriveHardFault

(User-specified Current
Fault)

E17

User-specified average current level has been exceeded.

DISABLE

NO

OverspeedFault

(Overspeed Fault)

E18

Motor speed has exceeded 125% of maximum rated speed.

DISABLE

NO

PositionErrorFault

(Excess Position Error)

E19

Axis position error limit has been exceeded. This fault can be configured
for status only.

DISABLE

Position Error

YES

MotFeedbackFault

(Motor Encoder State Error)

E20

The motor encoder encountered an illegal transition.

DISABLE

NO

AuxFeedbackNoiseFault

(Auxiliary Encoder State
Error)

E21

The auxiliary encoder encountered an illegal transition.

DISABLE

NO

OverloadFault

(Motor Thermal Protection
Fault)

E22

The internal filter protecting the motor from overheating has tripped.

DISABLE

NO

DriveOvertempFault

(IPM Thermal Protection
Fault)

E23

The internal filter protecting the drive from over heating has tripped.

DISABLE

Drive Thermal

YES

DriveHardFault

(Excess Velocity Error)

E24

Velocity error limit was exceeded.

DISABLE

NO

DriveHardFault

(Sensor Not Assigned)

E25

Homing or registration motion was attempted without a sensor
assigned.

DISABLE

NO

DriveHardFault

(User-specified Velocity
Fault)

E26

User-specified velocity level was exceeded.

DISABLE

NO

DriveHardFault

(Axis Not Homed)

E27

Absolute positioning was attempted without homing.

DISABLE

NO

DriveHardFault

(Motor Parameter Error)

E28

Parameter loaded from smart encoder or received from SERCOS
controller is incompatible with the drive.

DISABLE

NO

DriveHardFault

(Encoder Output Frequency
Exceeded)

E29

Encoder output frequency exceeds the maximum user-specified value.
This only applies when the encoder output is synthesized by the drive.

DISABLE

NO

DriveHardFault

(Encoder Communication
Fault)

E30

Communication was not established with an intelligent (i.e. Stegmann)
encoder on the motor feedback port.

DISABLE

NO

DriveHardFault

(Encoder Data)

E31

Encoder data is corrupted.

DISABLE

NO

DriveHardFault

(Sine/Cosine Encoder
Frequency Limit Exceeded)

E32

Maximum frequency of the sine/cosine circuitry has been exceeded.

DISABLE

NO

DriveHardFault

(Absolute Position Exceeds
Position Rollover)

E33

Absolute position exceeds position rollover.

DISABLE

NO

DriveHardFault

(Ground Fault)

E34

Excessive ground current in the converter was detected.

DISABLE

NO

Software Fault Message

Error

Code

Description

Drive Fault
Action/Attribute

RSLogix 5000
Programmable
Fault Action?

RSLogix 5000

(Ultraware)