Collecting Performance Data Chapter 3

The Part Id parameter tells FactoryTalk Metrics what type of part is
being produced by the activity area. Changes in the Part Id value

allow FactoryTalk Metrics to track what type of part is being
produced. If you always know what kind of part the activity area is
producing, you can obtain the OEE ratings for the activity area
sorted by part.

To configure the Part Id:

Under Part Id, in the Part Id Type list, select one of the following
options:

Do not monitor Part Id

Select this option if the application does not have information
about the types of parts the activity area is producing. The
OEE rating for the activity area will always be based on all
parts produced by the activity area.

Use a single Part Id

Select this option if the activity area produces only one type of
part, and the OEE rating for the activity area will always be
associated with that particular type of part.
In the Part Id box, type the part ID.

Monitor an Unscheduled data point for Part Id

Rockwell Automation Publication PLTMT-UM001M-EN-P-June 2014