Prerequisites — kawasaki robot, Related documentation, Establishing sensor/robot communication – Banner PresencePLUS Pro COLOR—PROII Camera User Manual

Page 65: Establishing, Sensor/robot communication

Advertising
background image

• Triggering the sensor and performing product changes
• Checking sensor status, such as pass, fail, and I/O line state
• Retrieving tool results, and sensor counters including pass/fail
• User-defined frame (command) delimiters and output field separators
• Logging input and output data to assist with RCC/MMI debugging

Prerequisites — Kawasaki Robot

This procedure assumes that you are using an Ethernet-enabled Kawasaki robot controller configuration such as:
• Kawasaki C Series Controller with a 1HA Ethernet board option
• Kawasaki D Series Controller with a 1KN or 1QN Ethernet board option
• Kawasaki D+ Series Controller with an integrated 1RA Ethernet board

Related Documentation

For more information relating to Banner's Vision Sensors and Kawasaki Robot Controllers, refer to the following

sources:
• Kawasaki Robot TCP/IP Function Instruction Manual
• Kawasaki D Series Controller AS Language Reference Manual
PresencePLUS electronic Help

Establishing Sensor/Robot Communication

Main Tasks to Complete

Step 1

Install and connect a
Presence
PLUS Vision
Sensor

1. Install Banner PresencePLUS Vision Sensor version 2009R1B or later.
2. Connect the Vision Sensor using one of the following approaches:

• connect to an existing Ethernet network via a switch or hub using a straight-through

Ethernet cable with RJ45 connectors

• connect directly to the Kawasaki controller using a cross-over Ethernet cable with RJ45

connectors.

3. Configure both the PresencePLUS sensor and the Kawasaki controller with static IP

addresses.

Main Tasks to Complete

Step 2

Configure
Presence
PLUS

1. Start the PresencePLUS software.
2. Connect to the sensor.

Ethernet ports:

The

65

Minneapolis, MN USA

Banner Engineering Corp.

System Setup Dialog

2/2010