When the [external in] is selected in, The program switch method -11 – KEYENCE IV Series User Manual

Page 187

Advertising
background image

6-11

- IV Series User's Manual (Monitor) -

Changeover for a Target (Program Functions)

When the [External IN] is selected in the Program Switch Method

1

Start the run mode.

“Starting an Operation” (Page 5-2)

2

Select the program number to which the product to be judged is registered with the status

of the input line.

Change the input lines IN2 to IN6 which were assigned to bit0 to bit4 in the input settings (Page 6-26)
to the following statuses and maintain the settings. Start the run mode with the new program number.

Program

number

bit4

(MSB) bit3

bit2

bit1

bit0

(LSB)

Program

number

bit4

(MSB) bit3

bit2

bit1

bit0

(LSB)

PROG00 OFF OFF OFF OFF OFF

PROG16 ON

OFF OFF OFF OFF

PROG01 OFF OFF OFF OFF ON

PROG17 ON

OFF OFF OFF ON

PROG02 OFF OFF OFF ON

OFF

PROG18 ON

OFF OFF ON

OFF

PROG03 OFF OFF OFF ON

ON

PROG19 ON

OFF OFF ON

ON

PROG04 OFF OFF ON

OFF OFF

PROG20 ON

OFF ON

OFF OFF

PROG05 OFF OFF ON

OFF ON

PROG21 ON

OFF ON

OFF ON

PROG06 OFF OFF ON

ON

OFF

PROG22 ON

OFF ON

ON

OFF

PROG07 OFF OFF ON

ON

ON

PROG23 ON

OFF ON

ON

ON

PROG08 OFF ON

OFF OFF OFF

PROG24 ON

ON

OFF OFF OFF

PROG09 OFF ON

OFF OFF ON

PROG25 ON

ON

OFF OFF ON

PROG10 OFF ON

OFF ON

OFF

PROG26 ON

ON

OFF ON

OFF

PROG11 OFF ON

OFF ON

ON

PROG27 ON

ON

OFF ON

ON

PROG12 OFF ON

ON

OFF OFF

PROG28 ON

ON

ON

OFF OFF

PROG13 OFF ON

ON

OFF ON

PROG29 ON

ON

ON

OFF ON

PROG14 OFF ON

ON

ON

OFF

PROG30 ON

ON

ON

ON

OFF

PROG15 OFF ON

ON

ON

ON

PROG31 ON

ON

ON

ON

ON

y

When the polarity (Page 6-28) is [NPN] ON : the state shorted with 0 V line

OFF : Open

y

When the polarity (Page 6-28) is [PNP] ON : the state that voltage is applied

OFF : Open

For details of the controlling method and the timing chart, refer to “Changing Over” (Page 7-7).

6

Useful Features/V

arious Functions

Advertising