Confirming/setting the ip address of the sensor, Confirming the router settings, Confirming/setting the ip address of – KEYENCE IV Series User Manual

Page 293: Confirming/setting the ip address of the

Advertising
background image

A-37

- IV Series User's Manual (Monitor) -

A

Remedy when the Monitor cannot be Connected with the Sensor

Confirming/Setting the IP address of

the sensor

Directly connect the sensor and monitor, and

confirm the IP address of the sensor.

After returning to the network connection, set

the confirmed IP address of the sensor, and then

confirm whether or not to connect with the sensor.

1

Directly connect the monitor and the

sensor of the confirmation/setting target.

“Connecting directly” (Page 2-16)
“When directly connecting with the sensor”

(Page 6-46)

2

Display the Sensor Setup Menu screen.

“Displaying the Sensor Setup Menu Screen”

(Page 6-7)

3

Tap the [Sensor Advanced] button.

4

Tap the [Environmental] button, and then

the [Network Settings] button.

5

Confirm the IP address of the sensor.

y

Tapping the [Edit] button displays the screen

to edit the address. Set the arbitrary address

and tap the [OK] button.

y

When the [Reset] button is tapped, the setup

values for the [IP Address], [Subnet Mask], and

[Default Gateway] will be reset and nothing will

be set. Again, set an arbitrary address.

6

After confirmation/setting is completed, tap

the [OK] button and exit from the network

settings.

7

Turn OFF the power and connect the

sensor and monitor via a network.

“Connecting via network” (Page 2-16)

8

Turn on the power.

z

z

If the monitor could be connected with the

sensor

The run screen opens.

z

z

If the monitor could not be connected with

the sensor

The Sensor Setup Menu screen opens. Set the

connection method etc. and connect with the

sensor.

“Remedy when connection via a network is

unavailable” (Page A-29)

Confirming the router settings

When a router is used, confirm that the following

port is opened.
Sensor : 63000 (default value)

For the setting methods of the sensor port

number, refer to the following.

“Network Settings” (Page 6-31)

y

BOOTP is fixed as 67 or 68.

y

The FTP port number can be changed on the

server. It is generally 20 or 21.