Firmware Package

Version and Date

Change

1.17.00, 01/13

•

Added French language support.

•

Increased the number of gates per logic level to 20.

•

Allow Grounded Delta Override to be effective regardless of configured
generator connection.

•

Increased the number of logic latches to 10.

•

Added phase rotation checks and pre-alarms.

•

Remote speed trim bias adjustable from analog input.

•

Added speed bias range in units of percent.

•

Added sequencing status display.

•

Added Ethernet kW and kvar sharing.

•

Phase Imbalance (47) disables in single-phase mode.

•

Improved response during Modbus writes.

•

Increased available configurable protection parameters.

•

Added system status display.

•

Modified breaker reset function so that breakers are only reset if
locked out, sync failed, or failed to open.

•

Added a setting to breaker fail pre-alarm to be active on transitions
only
or always.

•

Modified sequencing to operate correctly when units are operating due
to external ATS.

•

Corrected handling of Combined Code Red Alarm on ECU7/ECU8
engines.

•

Modified speed raise/lower so no change occurs if both conditions are
true.

•

Corrected potential settings loss in weak battery and emergency stop
scenarios.

1.15.00, 06/12

•

Added Russian language support.

•

Added Auto Breaker Operation Inhibit, Mains Fail Transfer Inhibit, and
Closed Transition Override logic elements.

•

Added Restart Delay setting.

•

Added SPN Conversion Method

•

Increased Max on Weak Battery and Low Battery Pre-alarms. 14 V for
12 V systems and 28 V for 24 V systems.

•

Added DPF Soot Level Pre-Alarms

•

Added DEF Fluid Level and Inducement Pre-Alarms

•

Added Unexpected Shutdown Alarm

•

Added function which disables the front panel buttons Run, Off, and
Auto when logic elements Run Mode, Off Mode, and Auto Mode are
set true.

•

Added 4 logic elements which override control of 4 LEDs on the
RDP-110.

1.13.08, 11/11

•

Made Diesel Particulate Filter Regeneration Request momentary.

•

Minor firmware improvements.