Generator parameter transmit enable data, Dpf manual regenerate data, Dpf regenerate disable data – Basler Electric DGC-2020 User Manual

Page 490: J1939 speed torque transmit enable data, Engine idle rpm data, Engine parameter transmit enable, Requested mtu smc eng operating mode, Spn conversion method, John deere regeneration interlock, Reserved

Advertising
background image

B-58

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

45318

Generator Parameter
Transmit Enable Data

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

45320

DPF Manual
Regenerate Data

Int32

N/A

N/A

RW

0 = Off
1 = On

45322

DPF Regenerate
Disable Data

Int32

N/A

N/A

RW

0 = Off
1 = On

45324

J1939 Speed Torque
Transmit Enable Data

Int32

N/A

N/A

RW

0 = Off
1 = On

45326

Engine Idle RPM Data

Int32

N/A

N/A

RW

100 - 2000

45328

Engine Parameter
Transmit Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

45330

Requested MTU SMC
ENG Operating Mode

Int32

N/A

N/A

RW

1 - 2

45332

SPN Conversion
Method

Int32

N/A

N/A

RW

1 - 4

45334

John Deere
Regeneration Interlock

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

45334-
482

RESERVED

45484

Volt Reg CAN bus
Param Transmit Enable
Data

Int32

N/A

N/A

RW

0 = None
1 = Marathon
2 = Basler
3 = J1939

45486

Volt Reg Primary Volt
Setpoint in DeciVolts
Data

Int32

DeciUnit

Deci

RW

1000 - 6000

45488

Volt Reg Alternate Volt
Setpoint in DeciVolts
Data

Int32

DeciUnit

Deci

RW

1000 - 6000

45490

Volt Reg Volt Adjust
Bandwidth CentiVolts
Data

Int32

CentiUnit

Centi

RW

0 - 3000

45492

Volt Reg Field Current
in Milliamps Data

Int32

MilliUnit

Milli

RW

0 - 30000

45494

Volt Reg Primary UF
Knee in DeciHertz Data

Int32

DeciUnit

Deci

RW

400 - 700

45496

Volt Reg Alternate UF
Knee in DeciHertz Data

Int32

DeciUnit

Deci

RW

400 - 700

45498

Volt Reg Underfreq
Slope in CentiUnits

Int32

CentiUnit

Centi

RW

100 - 500

45500

Analog Input 1 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45502

Analog Input 2 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45504

Analog Input 3 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45506

Analog Input 4 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45508

Analog Input 5 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45510

Analog Input 6 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45512

Analog Input 7 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45514

Analog Input 8 Metering
Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45516

RTD Input 1 Metering
Value

Int32

CentiDeg F

Centi

R

(-100000000) – 99999900

45518

RTD Input 2 Metering
Value

Int32

CentiDeg F

Centi

R

(-100000000) – 99999900

45520

RTD Input 3 Metering
Value

Int32

CentiDeg F

Centi

R

(-100000000) – 99999900

45522

RTD Input 4 Metering
Value

Int32

CentiDeg F

Centi

R

(-100000000) – 99999900

Advertising