Basler Electric DGC-2020 User Manual
Page 255

Name
Description
Symbol
MODEM
(Optional)
Connect the input to the output of another logic block.
When true, the modem dials out.
MTUCYLCUTOUT-
DISABLE
(MTU Cylinder Cutout
Disable)
When this logic element is true, Cylinder Cutout Disable 1
and Cylinder Cutout Disable 2 are both sent to the engine
ECU with true status. When this logic element is false,
Cylinder Cutout Disable 1 and Cylinder Cutout Disable 2
are sent to the engine ECU with states set by the values
programmed for the Cylinder Cutout Disable 1 and
Cylinder Cutout Disable 2 DGC-2020 settings which are
configured on the ECU Setup screen in BESTCOMSPlus.
MTUSPDDMDSW
This logic element can be used to specify the Speed
Demand Source parameter value that is sent to an MTU
Engine ECU. When no input is true, the value sent to the
engine ECU is the value specified in the Speed Demand
Source setting in the ECU configuration setting. If an input
on this logic element is true, the selected Speed Demand
Source will be sent rather than the value specified by the
Speed Demand Source setting.
Analog CAN: This input configures the MTU ECU to
accept speed bias requests over J1939 CANBus from the
DGC-2020.
Up Down ECU: This input configures the MTU ECU to
accept speed raise/lower commands via contact inputs on
the ECU.
Up Down CAN: This input configures the MTU ECU to
accept speed raise/lower commands via communications
over J1939 CAN bus.
Analog ECU: This input configures the MTU ECU to
accept speed bias via bias voltage input connections on
the ECU.
Frequency: This configures the MTU ECU to accept speed
commands via a frequency signal input on the ECU. The
mapping of input signal frequency to machine speed is
configured in a curve within the engine ECU.
No CAN Demand: This input configures the MTU ECU to
disregard all speed requests or speed raise/lower requests
from J1939 CAN bus.
OFFMODE
When this input is true, the DGC-2020 will switch to OFF
mode. This is a pulsed input. It does not need to be held
after the desired mode switch has occurred.
9400200990 Rev X
DGC-2020 BESTlogic
™
Plus Programmable Logic
5-27