Protection alarm metering, Cumulative stats - total run minutes, Cumulative stats - loaded run minutes – Basler Electric DGC-2020 User Manual

Page 476: Cumulative stats - unloaded run minutes, Run stats - total run minutes, Run stats - loaded run minutes, Run stats - unloaded run minutes

Advertising
background image

B-44

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44934-35

Protection Alarm
Metering

Int32

N/A

N/A

R

Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = 81 ROC DF/DT Trip
Bit 19 = 78 Vector Shift Trip
Bit 20 = 51-3 Overcurrent
Bit 21 = 40Q Loss of Excitation
Bit 22 = 32 Reverse Power
Bit 23 = 59-2 Overvoltage
Bit 24 = 27-2 Undervoltage
Bit 25 = 51-2 Overcurrent
Bit 26 = 81 Underfrequency
Bit 27 = 81 Overfrequency
Bit 28 = 59-1 Overvoltage
Bit 29 = 27-1 Undervoltage
Bit 30 = 47 Phase Imbalance
Bit 31 = 51-1 Overcurrent

44936

Cumulative Stats - Total
Run Minutes

Uint32

Minute

N/A

RW

0 - 5999940

44938

Cumulative Stats -
Loaded Run Minutes

Uint32

Minute

N/A

RW

0 - 5999940

44940

Cumulative Stats -
Unloaded Run Minutes

Uint32

Minute

N/A

RW

0 - 5999940

44942

Run Stats - Total Run
Minutes

Uint32

Minute

N/A

RW

0 - 5999940

44944

Run Stats - Loaded Run
Minutes

Uint32

Minute

N/A

RW

0 - 5999940

44946

Run Stats - Unloaded
Run Minutes

Uint32

Minute

N/A

RW

0 - 5999940