Firmware Package

Version and Date

Change

1.09.00, 07/09

Corrected transmittal of parameters to engine for MDEC module types
201, 302, and 303.

Implemented most recent MTU fault codes.

Engine Total Run Time in metering now displays hours and minutes.
Engine Total Run Time previously displayed hours only.

Added front panel diagnostics to show Modbus Read Count, Modbus
Write Count, and Serial Flash Write Count.

Modbus

 legacy registers 40019 and 40020 are now read/write.

Previously these registers were write only.

Improved MCS5 parameter handling.

Fixed spurious High Charge Air Temp Pre-Alarm every time engine
starts on MTU-ECU7 machines.

Accelerator pedal position is now sent to Volvo ECU for load sharing.

Modified generator breaker logic to allow closure of generator breaker
from a dead gen to a dead bus (if Dead Bus Close Enable is selected).
In previous versions of firmware, closure of the generator breaker from
a dead generator was not possible.

1.08.01, 01/09

Added support for CEM-2020H.

Changed time dial range of 51 element fixed time curve from 0-30 s to
0-7,200 s.

Added Phase Toggle Delay setting for front panel HMI.

Added Off Mode Cooldown feature.

Added 51-3 element.

Added Var/PF control.

Added LSM Input settings.

Added Checksum Fail and CEM Hardware Mismatch pre-alarms.

Added kvar A, B, C, and Total metering.

Added several MTU items to metering.

Re-arranged CANbus Setup screens and added ECU Setup screens
on front panel HMI.

Added “P” (programmable) curve selection for the 51 function.

1.07.02, 09/08

Finalized settings for AEM-2020.

1.06.00, 07/08

Added settings for AEM-2020.

Added settings for Automatic Generator Detection.

Added settings for Integrating Reset on 51 function.

Added settings for Configurable Protection.

1.05.00, 04/08

Added settings for CEM-2020.

1.04.00, 12/07

Added settings for LSM-2020.

1.03.00, 08/07

Added 32 and 40Q protection functions.

Added Automatic Restart function and Exercise Timer.

Added dual settings for 51, 27, and 59 functions.

Added Oil Pressure Crank Disconnect Enable.

Modified Prestart operation during rest cycle.

Added 2 additional Engine kW Overload Pre-Alarms.

Added Low Line Scale Factor for EPS Supplying Load and Engine kW
Overload Pre-Alarms.

Changed the metering range of coolant temperature to 32-410 F.

Changed the Low-Coolant Temp Pre-Alarm range to 32-150 F.

1.02.00, 05/07

Added Spanish language support.

1.00.08, 03/07

Minor firmware improvements.

1.00.07, 01/07

Added Chinese language support.